  "tool": "thermaloptimizer",
  "file": "thermaloptimizer.html",
  "manifest_revision": "2026-09-06b",
  "reference": "Canonical Thermal System Optimizer v0.71 scoped benchmark suite: published psychrometric, terminal-emission, borefield, borehole-resistance and steam-property references plus closed-form heat-exchanger, hydraulics and economics identities.",
  "reference_citations": [
    "PsychroLib API example / ASHRAE Handbook Fundamentals 2017 — 25 °C dry bulb, 80 % RH -> dew point 21.309397163661785 °C (https://psychrometrics.github.io/psychrolib/api_docs.html)",
    "CIBSE Guide B / BS EN 1264 basic characteristic — q = 8.92 (t_fm - t_i)^1.1 (https://ierga.com/hr/wp-content/uploads/sites/2/2017/10/CIBSE-Guide-B-Heating-Ventilating-Air-Conditioning-And-Refrigeration-Fixed.pdf)",
    "Kermi convector technical data / EN 442 logarithmic conversion — Phi = Phi_SL (Delta t_ln / 49.83)^n; Delta t_ln logarithmic mean excess (https://radiaatorikeskus.ee/wp-content/uploads/2023/10/Kermi-konvektorite-tehniline-andmeleht-ENG.pdf)",
    "Counterflow epsilon-NTU equal-capacity limit — epsilon = NTU/(1+NTU) for C*=1; NTU=1 -> 0.5",
    "Gnielinski 1976 internal turbulent-flow correlation — Heat Transfer 1.2.0 documented example: Re=1e5, Pr=1.2, Darcy f=0.0185 -> Nu=254.62682749359632 (https://ht.readthedocs.io/en/release/_modules/ht/conv_internal.html)",
    "Darcy laminar friction identity — f_D = 64/Re; Re=1000 -> 0.064",
    "pygfunction finite_line_source example — H1=H2=150 m, D1=D2=4 m, distance=5 m, alpha=1e-6 m2/s, t=4 weeks -> h=0.0110473635393 (https://pygfunction.readthedocs.io/en/stable/modules/heat_transfer.html)",
    "ASHRAE Handbook Geothermal Energy, Example 2 — 3x2 field; T0=15 C, k=1.5 W/mK, 10 y extraction 5 W/m, g=12.3 -> Tb=8.5 C (https://handbook.ashrae.org/Handbooks/A15/SI/a15_ch34/a15_ch34_si.aspx)",
    "ASHRAE Handbook 2023 Chapter 35 Table 5 — 25 mm DR11 HDPE single U-tube, location B, 100 mm bore, Re=4000, grout k=1.40 W/(m K) -> Rb=0.14 m K/W (https://handbook.ashrae.org/Handbooks/A23/SI/A23_Ch35/a23_ch35_si.aspx)",
    "pygfunction g-function module uniform_temperature example — two vertical boreholes H=150 m, D=4 m, rb=0.075 m, spacing=5 m, alpha=1e-6 m2/s; t=1e7 s -> g=4.33406497 (https://pygfunction.readthedocs.io/en/v2.0.0/gfunction.html)",
    "pygfunction 2.0 uniform_temperature time-series example — two 150 m boreholes, 5 m spacing, 12 equal segments; t=1e4..1e11 s published g-function array (https://pygfunction.readthedocs.io/en/v2.0.0/gfunction.html)",
    "CoolProp 8.0.0 High-Level Interface saturation example — Water at 1 atm: saturated vapor h=2675529.32550072 J/kg, saturated liquid h=419057.7330939922 J/kg; latent heat=2256471.592406728 J/kg (https://coolprop.org/coolprop/HighLevelAPI.html)",
    "Level annuity present-value identity — PV = C(1-(1+r)^-N)/r"
  ],
  "reference_provenance": "recorded",
  "tolerance": "Per-case absolute or relative tolerances recorded in each benchmark case.",
  "run_at": "2026-09-04T14:10:32Z",
  "total": 13,
  "passed": 13,
  "failed": 0,
  "flagged": 0,
  "independent_validation": false,
  "cases": [
    {
      "id": "BM-PSY-001",
      "group": "psychrometrics",
      "kind": "published-reference",
      "note": "PsychroLib documents this numerical example and states that its equations implement ASHRAE Handbook—Fundamentals.",
      "pass": true,
      "actual": 21.30939716332975,
      "expected": 21.309397163661785,
      "absolute_error": 3.320366204206948e-10,
      "tolerance": {
        "abs": 1e-06
      },
      "source": {
        "title": "PsychroLib API example / ASHRAE Handbook Fundamentals 2017",
        "url": "https://psychrometrics.github.io/psychrolib/api_docs.html",
        "reference": "25 °C dry bulb, 80 % RH -> dew point 21.309397163661785 °C"
      }
    },
    {
      "id": "BM-FLOOR-001",
      "group": "floor-emission",
      "kind": "published-equation",
      "note": "General-area surface limit example: 29 °C floor, 20 °C room gives about 100 W/m².",
      "pass": true,
      "actual": 100.00727983233375,
      "expected": 100.00727983233375,
      "absolute_error": 0,
      "tolerance": {
        "rel": 1e-12
      },
      "source": {
        "title": "CIBSE Guide B / BS EN 1264 basic characteristic",
        "url": "https://ierga.com/hr/wp-content/uploads/sites/2/2017/10/CIBSE-Guide-B-Heating-Ventilating-Air-Conditioning-And-Refrigeration-Fixed.pdf",
        "reference": "q = 8.92 (t_fm - t_i)^1.1"
      }
    },
    {
      "id": "BM-RAD-001",
      "group": "radiator-emission",
      "kind": "published-equation",
      "note": "Reference data from an EN 442 chamber example: Phi_SL=1979 W, n=1.2803; evaluated at 40/33/20 °C with the published logarithmic law.",
      "pass": true,
      "actual": 471.39623610371854,
      "expected": 471.39623610371854,
      "absolute_error": 0,
      "tolerance": {
        "abs": 1e-06
      },
      "source": {
        "title": "Kermi convector technical data / EN 442 logarithmic conversion",
        "url": "https://radiaatorikeskus.ee/wp-content/uploads/2023/10/Kermi-konvektorite-tehniline-andmeleht-ENG.pdf",
        "reference": "Phi = Phi_SL (Delta t_ln / 49.83)^n; Delta t_ln logarithmic mean excess"
      }
    },
    {
      "id": "BM-HX-001",
      "group": "heat-exchanger",
      "kind": "closed-form-identity",
      "note": "",
      "pass": true,
      "actual": 0.5,
      "expected": 0.5,
      "absolute_error": 0,
      "tolerance": {
        "abs": 1e-12
      },
      "source": {
        "title": "Counterflow epsilon-NTU equal-capacity limit",
        "reference": "epsilon = NTU/(1+NTU) for C*=1; NTU=1 -> 0.5"
      }
    },
    {
      "id": "BM-HX-FILM-001",
      "group": "heat-exchanger-film",
      "kind": "published-reference",
      "note": "Published-correlation regression for the new tube-side film model; Gnielinski validity is bounded to 0.5 < Pr <= 2000 and 2300 <= Re <= 5e6 in the cited implementation.",
      "pass": true,
      "actual": 254.62682749359632,
      "expected": 254.62682749359632,
      "absolute_error": 0,
      "tolerance": {
        "abs": 1e-10
      },
      "source": {
        "title": "Gnielinski 1976 internal turbulent-flow correlation",
        "url": "https://ht.readthedocs.io/en/release/_modules/ht/conv_internal.html",
        "reference": "Heat Transfer 1.2.0 documented example: Re=1e5, Pr=1.2, Darcy f=0.0185 -> Nu=254.62682749359632"
      }
    },
    {
      "id": "BM-HYD-001",
      "group": "hydraulics",
      "kind": "closed-form-identity",
      "note": "",
      "pass": true,
      "actual": 0.064,
      "expected": 0.064,
      "absolute_error": 0,
      "tolerance": {
        "abs": 1e-12
      },
      "source": {
        "title": "Darcy laminar friction identity",
        "reference": "f_D = 64/Re; Re=1000 -> 0.064"
      }
    },
    {
      "id": "BM-FLS-001",
      "group": "finite-line-source",
      "kind": "published-reference",
      "note": "Independent numerical check of the vertical FLS primitive used for geometry-generated screening response tables.",
      "pass": true,
      "actual": 0.011047363539468983,
      "expected": 0.0110473635393,
      "absolute_error": 1.6898288324185273e-13,
      "tolerance": {
        "abs": 2e-08
      },
      "source": {
        "title": "pygfunction finite_line_source example",
        "url": "https://pygfunction.readthedocs.io/en/stable/modules/heat_transfer.html",
        "reference": "H1=H2=150 m, D1=D2=4 m, distance=5 m, alpha=1e-6 m2/s, t=4 weeks -> h=0.0110473635393"
      }
    },
    {
      "id": "BM-GROUND-001",
      "group": "borefield-g-function",
      "kind": "published-reference",
      "note": "Direct check of the published g-function temperature-response relation.",
      "pass": true,
      "actual": 8.47464733323229,
      "expected": 8.5,
      "absolute_error": 0.02535266676770931,
      "tolerance": {
        "abs": 0.05
      },
      "source": {
        "title": "ASHRAE Handbook Geothermal Energy, Example 2",
        "url": "https://handbook.ashrae.org/Handbooks/A15/SI/a15_ch34/a15_ch34_si.aspx",
        "reference": "3x2 field; T0=15 C, k=1.5 W/mK, 10 y extraction 5 W/m, g=12.3 -> Tb=8.5 C"
      }
    },
    {
      "id": "BM-RB-001",
      "group": "borehole-resistance",
      "kind": "published-table",
      "note": "Exact provenance-bearing table lookup; it validates the supported library point, not arbitrary borehole-resistance prediction.",
      "pass": true,
      "actual": 0.14,
      "expected": 0.14,
      "absolute_error": 0,
      "tolerance": {
        "abs": 1e-12
      },
      "source": {
        "title": "ASHRAE Handbook 2023 Chapter 35 Table 5",
        "url": "https://handbook.ashrae.org/Handbooks/A23/SI/A23_Ch35/a23_ch35_si.aspx",
        "reference": "25 mm DR11 HDPE single U-tube, location B, 100 mm bore, Re=4000, grout k=1.40 W/(m K) -> Rb=0.14 m K/W"
      }
    },
    {
      "id": "BM-UBWT-001",
      "group": "borefield-segmented-UBWT",
      "kind": "published-reference",
      "note": "Legacy pygfunction 2.0 numerical point uses 12 equal segments; this validates one time point, not spatial convergence.",
      "pass": true,
      "actual": 4.334032386204888,
      "expected": 4.33406497,
      "absolute_error": 3.2583795111840175e-05,
      "tolerance": {
        "abs": 5e-05
      },
      "source": {
        "title": "pygfunction g-function module uniform_temperature example",
        "url": "https://pygfunction.readthedocs.io/en/v2.0.0/gfunction.html",
        "reference": "two vertical boreholes H=150 m, D=4 m, rb=0.075 m, spacing=5 m, alpha=1e-6 m2/s; t=1e7 s -> g=4.33406497"
      }
    },
    {
      "id": "BM-UBWT-002",
      "group": "borefield-segmented-UBWT-transient",
      "kind": "published-reference",
      "note": "Validates transient BC-III load redistribution and temporal superposition over eight decades of time for the published geometry.",
      "pass": true,
      "actual": 8.782198079870795e-08,
      "expected": 0,
      "absolute_error": 8.782198079870795e-08,
      "tolerance": {
        "abs": 2e-07
      },
      "source": {
        "title": "pygfunction 2.0 uniform_temperature time-series example",
        "url": "https://pygfunction.readthedocs.io/en/v2.0.0/gfunction.html",
        "reference": "two 150 m boreholes, 5 m spacing, 12 equal segments; t=1e4..1e11 s published g-function array"
      }
    },
    {
      "id": "BM-PH-001",
      "group": "steam-condensation-p-h",
      "kind": "published-reference",
      "note": "Validates enthalpy-difference steam/condensate interface and explicitly avoids constant-cp treatment through phase change.",
      "pass": true,
      "actual": 2256471.592406728,
      "expected": 2256471.592406728,
      "absolute_error": 0,
      "tolerance": {
        "abs": 1e-06
      },
      "source": {
        "title": "CoolProp 8.0.0 High-Level Interface saturation example",
        "url": "https://coolprop.org/coolprop/HighLevelAPI.html",
        "reference": "Water at 1 atm: saturated vapor h=2675529.32550072 J/kg, saturated liquid h=419057.7330939922 J/kg; latent heat=2256471.592406728 J/kg"
      }
    },
    {
      "id": "BM-ECO-001",
      "group": "economics",
      "kind": "closed-form-identity",
      "note": "",
      "pass": true,
      "actual": 12721.73492918481,
      "expected": 12721.734929184819,
      "absolute_error": 9.094947017729282e-12,
      "tolerance": {
        "rel": 1e-12
      },
      "source": {
        "title": "Level annuity present-value identity",
        "reference": "PV = C(1-(1+r)^-N)/r"
      }
    }
  ],
  "not_benchmarked": [
    "generic heat-pump quality factors/capacity derating",
    "candidate topology search",
    "8760 dispatch policy",
    "2R2C parameter defaults",
    "cost defaults",
    "refrigerant property backend/state generation"
  ],
  "notes": [